• Rpm65 Power Quality Analyser Network
  • Rpm65 Power Quality Analyser Network
  • Rpm65 Power Quality Analyser Network
  • Rpm65 Power Quality Analyser Network
  • Rpm65 Power Quality Analyser Network
  • Rpm65 Power Quality Analyser Network

Rpm65 Power Quality Analyser Network

After-sales Service: 2 Years
Warranty: 2 Years
Display: Digital
Installation: Direct Connected
Usage: Multi-Functional Energy Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Maximum Demand Meter, Power Quality Analyser
Electric Equipment: Single-Phase, Two-Phase, Three-Phase
Customization:
Manufacturer/Factory & Trading Company
Diamond Member Since 2023

Suppliers with verified business licenses

Guangdong, China
to see all verified strength labels (24)
  • Overview
  • Product Description
  • Product Parameters
  • Installation Instructions
  • Company Profile
Overview

Basic Info.

Model NO.
RPM65
Theory
Electronic Meter
Power Meter Connection
Terminal
Measured Signal
Continuous Wave
Type
Power Meter
Certification
RoHS, ISO, CE
Customized
Customized
Power Consumption
4vamax
Operating Voltage (Un)
85~265 VAC 50/60Hz (Depend on Order)
CT Inputs
4 Current Input: 0.05-5.5A
Voltage Inputs
4 Voltage Input : Max 690VAC (L-L)
Transport Package
Carton Box
Specification
96*96
Trademark
Romaz
Origin
China
HS Code
9030390000
Production Capacity
50000PCS/Month

Product Description

Product Description

Rpm65 Power Quality Analyser Network
*T rue RMS measurements (512 samples/cycle)
For single-phase, two-phase, three-phase system
   Measurements: VL-L, VL-N, I, In, Cos , Pf, Hz, W, ∑W, Va, ∑Va, Var, ∑Var, import Kwh, export Kwh,import Kvarh, export Kvarh, V-THD,
   I-THD,1-63th harmonic, system running hours, % voltage unbalance, %current unbalance, % system load, total frequency.
3 voltage and 4 current input (Measure or calculate the neutral current)
Voltage Input: 0-690Vac, Current input: 1 or 5A CT selective
% system load and system running hours
Detects CT wiring errors
Maximum, minimum and demand for U, I, P, Q, S in hours, days, months
Real time clock with integrated backup rechargeable battery
4 quadrants energy measurement , 4 tariffe energy measurement and  monthly energy calculation
2 pulse output and RS485 communication: Modbus RTU
Waveforms and phase diagram for voltage, current
Alarm event log
Micro SD(support 32GB) for data logger
Data recorded in standard excel file formats for further EN50160 analysis
English, Chinese (traditional & simplied)
Moduel function options (only one can be selected)
   - 7 digital input +2 relay output(remote or alarm)(Standard)
   - 7 digital input +2 analog output(4-20mA) for V1,V2,V3,V12,V23,V31,I1,I2,I3 (option)
   - Ethernet (Modbus TCP), Web server+2 digital input +2 relay output(remote or alarm) (option)
   - LoRa wireless (Private protocol)+2 digital input+2 relay output (remote or alarm)(option) 
   - RS-485 interface (Modbus RTU)+2 digital input+2 relay output (remote or alarm)(option)
   - WIFI wireless +2 digital input +2 relay output(remote or alarm) (option)

Product Parameters

Auxiliary Supply
Operating voltage (Un) 85···265 VAC 50/60Hz 10W / 100-285VDC/24-48VDC(depend on order)
Power consumption 4VA max
Measurement input
Voltage inputs for direct connection: Phase-neutral(L-N): max 400V RMS CAT III
Input impedance(for direct voltage inputs): >4MΩ
CT inputs: max 5.5A RMS
CT inputs overload capacity: max 10A
CT inputs Self-consumption : <0.2VA
Accuracy
Three phase voltage: ± 0.2%
Currents: ± 0.2%
Powers: ± 0.5%
Powers factor: ± 0.5%
Frequency: ± 0.02%
Harmonics: ± 1%
Active energy: Class 0.5S
Reactive energy: Class 0.5S
Insulation
Insulation voltage
3kV for 1 min., 50Hz
Display
Display type
3.2inch 240x160 pix
I/O
Digital inputs:
Active dry contact
Digital outputs:
2 Relay N/O 220VAC 5A
Analog outputs:
4-20mADC / max load 500Ω
Pulse output:
24-30VDC Max.50mA, Min. 50msec pulse width
Memory  
Recording memory:
max 32 GB SD (TF)
Communication
Ethernet port:
Auto MDIX Rj45 10/100 Base Ethernet
RS-485 port:
1 optoisolated, 4800-57600
Protocols:
HTTP, HTTPS, Modbus RTU/TCP
Environmental conditions
Opterating temperature:
-10···+55°C
Storage temperature:
-25···+75°C
Relative humidity:
95% max without condensing
Altitude:
max 2000m AMSL
Installation & use:
Internal
Mechanical characteristics
Mounting:
Panel mount 96x96mm(The panel cut-size 92*92mm)
Size:
Front(WXH)96x96mm, Rear (HxD) 90x70mm
Degree of protection:
IP40(optional IP54) on front, IP20 housing and terminals
Weight:
400g
Standard compliance
reference standard:
IEC61010-1; IEC61557-1;IEC61557-12; IEC61326-1;IEC62053-21;
IEC62053-22; IEC62053-31; IEC60068-2-1; IEC60068-2-30;
IEC60364-5-52; IEC61000-3-2; IEC61000-3-3; IEC61000-4-2;
IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6;
IEC61000-4-8; IEC61000-4-11; IEC61000-4-30

Rpm65 Power Quality Analyser Network

Installation Instructions

Rpm65 Power Quality Analyser Network

Company Profile

Rpm65 Power Quality Analyser Network

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2023

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
11
Year of Establishment
2020-12-09