Customization: | Available |
---|---|
After-sales Service: | 2 Years |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Auxiliary Supply | |
Operating voltage (Un) | 85···265 VAC 50/60Hz |
Power consumption | 4VA max |
Measurement input | |
Voltage inputs for direct connection: | Phase-neutral(L-N): max 400V RMS CAT III |
Input impedance(for direct voltage inputs): | >4MΩ |
CT inputs: | max 5.5A RMS |
CT inputs overload capacity: | max 10A |
CT inputs Self-consumption : | <0.2VA |
Accuracy | |
Three phase voltage: | ± 0.5% |
Currents: | ± 0.5% |
Powers factor: | ± 0.5% |
Frequency: | ± 0.02% |
Insulation | |
Insulation voltage
|
3kV for 1 min., 50Hz
|
Display | |
Display type
|
14.2mm LED red digital tube
|
Communication | |
RS-485 port:
|
1 optoisolated, 4800-57600
|
Protocols:
|
Modbus RTU
|
Environmental conditions | |
Opterating temperature:
|
-10···+55°C
|
Storage temperature:
|
-25···+75°C
|
Relative humidity:
|
95% max without condensing
|
Altitude:
|
max 2000m AMSL
|
Installation & use:
|
Internal
|
Mechanical characteristics | |
Mounting:
|
Panel mount 96x96mm(The panel cut-size 92*92mm)
|
Size:
|
Front(WXH)96x96mm, Rear (HxD) 90x70mm
|
Degree of protection:
|
IP40(optional IP54) on front, IP20 housing and terminals
|
Weight:
|
400g
|
Standard compliance | |
reference standard: |
IEC61010-1; IEC61557-12;
IEC61326-1; EN55011
IEC61000-3-2; IEC61000-3-3;
IEC61000-4-2; IEC61000-4-3;
IEC61000-4-4; IEC61000-4-5;
IEC61000-4-6; IEC61000-4-8;
IEC61000-4-11; IEC61000-4-30
|